Using a Micrologic Relay in an ACB for Restricted Earth Fault (REF) Protection

Schneider Micrologic 6.0x With restricted Earth Fault relay

Using a Micrologic Relay in an ACB for Restricted Earth Fault (REF) Protection

Modern ACB protection units such as Micrologic trip units from Schneider Electric allow REF-style protection using residual current measurement and external CT arrangements. While Micrologic isn’t a traditional standalone REF relay, it can be configured to provide zone-based earth fault protection when installed correctly.


πŸ”§ What REF Protection Is Doing in This Application

Restricted Earth Fault protection is designed to:

βœ… Detect internal earth faults inside a defined protection zone

βœ… Ignore external earth faults downstream or upstream

βœ… Provide fast trip times for safety and equipment protection

Typical zones include:

  • Generator windings
  • Transformer LV windings
  • Busbar sections
  • Incomer sections of LV boards

⚑ How Micrologic Achieves REF-Type Protection

Micrologic units typically use residual earth fault measurement, meaning:

The relay monitors:

Ia + Ib + Ic (+ In if present) = Residual Current

If the sum β‰  0 β†’ Earth leakage detected β†’ Trip output operates.

To achieve REF-style protection (restricted zone protection), you normally:

1️⃣ Use External Core Balance CT (CBCT) or Residual CT Arrangement

Installed around:

  • All phase conductors
  • Neutral (if present)

This ensures only earth faults inside the protected zone are detected.


2️⃣ Wire CT Secondary Into Micrologic Earth Fault Input

Depending on Micrologic version (P / H / X):

You configure:

  • Earth fault pickup current (Ig)
  • Earth fault delay time (Tg)
  • Trip curve characteristics

For REF-style protection you normally use:

βœ” Low pickup setting

βœ” Fast or instantaneous operation


3️⃣ Define the Protection Zone Physically

The CT location defines the zone:

If CT is installed:

  • After breaker β†’ Protects downstream equipment only
  • Before breaker β†’ Protects busbar + breaker + connections

Correct positioning is critical.


🧠 Example REF-Type Application Using Micrologic

LV Incomer Protecting Transformer Secondary

Setup:

Transformer β†’ CT Zone β†’ ACB β†’ LV Busbar

Micrologic monitors earth leakage only inside this zone.

If earth fault occurs inside:

βœ” Trips instantly

If fault occurs downstream:

βœ” Other protection clears fault

βœ” ACB stays closed


πŸ”‹ Generator Application Example

Micrologic can be used when protecting:

  • Generator LV output
  • Generator breaker incomer

Using:

  • CBCT around generator phase conductors
  • Earth fault element configured low sensitivity

This provides early detection of winding insulation faults.


πŸ“Š Advantages of Using Micrologic for REF-Type Protection

βœ” Integration

No separate REF relay needed in many LV systems.

βœ” Cost Effective

Less panel space

Less wiring

Lower install cost

βœ” Communication & Monitoring

Modern Micrologic allows:

  • Event logging
  • Fault recording
  • Network comms
  • BMS / SCADA integration

⚠️ Important Engineering Considerations

CT Matching

Incorrect CT ratios can cause:

❌ Nuisance tripping

❌ Protection failure


Stability During Through Faults

Must ensure CT saturation doesn’t create false residual current.


Neutral Considerations

If system has neutral:

Neutral must pass through CT window.


Earthing System Type Matters

Different approach for:

  • TN-S
  • TN-C-S
  • IT systems
  • Generator island mode

πŸ—οΈ Where This Is Commonly Used

βœ” LV Incomers feeding critical busbars

βœ” Generator incomer breakers

βœ” Transformer LV secondary protection

βœ” Data centres

βœ” Industrial process plants


πŸ› οΈ How NKD-Type Integrators Typically Implement This

In real projects this usually involves:

  • Selecting correct Micrologic variant
  • Designing CT placement
  • Setting earth fault pickup + delay
  • Functional trip testing
  • Injection testing
  • Coordination with upstream HV protection

πŸ‘ When to Use Dedicated REF Relay Instead

Still recommended when:

  • HV transformer differential schemes
  • Generator primary protection
  • High stability protection required
  • Multiple CT schemes required