Using a Micrologic Relay in an ACB for Restricted Earth Fault (REF) Protection
Modern ACB protection units such as Micrologic trip units from Schneider Electric allow REF-style protection using residual current measurement and external CT arrangements. While Micrologic isnβt a traditional standalone REF relay, it can be configured to provide zone-based earth fault protection when installed correctly.
π§ What REF Protection Is Doing in This Application
Restricted Earth Fault protection is designed to:
β Detect internal earth faults inside a defined protection zone
β Ignore external earth faults downstream or upstream
β Provide fast trip times for safety and equipment protection
Typical zones include:
- Generator windings
- Transformer LV windings
- Busbar sections
- Incomer sections of LV boards
β‘ How Micrologic Achieves REF-Type Protection
Micrologic units typically use residual earth fault measurement, meaning:
The relay monitors:
Ia + Ib + Ic (+ In if present) = Residual Current
If the sum β 0 β Earth leakage detected β Trip output operates.
To achieve REF-style protection (restricted zone protection), you normally:
1οΈβ£ Use External Core Balance CT (CBCT) or Residual CT Arrangement
Installed around:
- All phase conductors
- Neutral (if present)
This ensures only earth faults inside the protected zone are detected.
2οΈβ£ Wire CT Secondary Into Micrologic Earth Fault Input
Depending on Micrologic version (P / H / X):
You configure:
- Earth fault pickup current (Ig)
- Earth fault delay time (Tg)
- Trip curve characteristics
For REF-style protection you normally use:
β Low pickup setting
β Fast or instantaneous operation
3οΈβ£ Define the Protection Zone Physically
The CT location defines the zone:
If CT is installed:
- After breaker β Protects downstream equipment only
- Before breaker β Protects busbar + breaker + connections
Correct positioning is critical.
π§ Example REF-Type Application Using Micrologic
LV Incomer Protecting Transformer Secondary
Setup:
Transformer β CT Zone β ACB β LV Busbar
Micrologic monitors earth leakage only inside this zone.
If earth fault occurs inside:
β Trips instantly
If fault occurs downstream:
β Other protection clears fault
β ACB stays closed
π Generator Application Example
Micrologic can be used when protecting:
- Generator LV output
- Generator breaker incomer
Using:
- CBCT around generator phase conductors
- Earth fault element configured low sensitivity
This provides early detection of winding insulation faults.
π Advantages of Using Micrologic for REF-Type Protection
β Integration
No separate REF relay needed in many LV systems.
β Cost Effective
Less panel space
Less wiring
Lower install cost
β Communication & Monitoring
Modern Micrologic allows:
- Event logging
- Fault recording
- Network comms
- BMS / SCADA integration
β οΈ Important Engineering Considerations
CT Matching
Incorrect CT ratios can cause:
β Nuisance tripping
β Protection failure
Stability During Through Faults
Must ensure CT saturation doesnβt create false residual current.
Neutral Considerations
If system has neutral:
Neutral must pass through CT window.
Earthing System Type Matters
Different approach for:
- TN-S
- TN-C-S
- IT systems
- Generator island mode
ποΈ Where This Is Commonly Used
β LV Incomers feeding critical busbars
β Generator incomer breakers
β Transformer LV secondary protection
β Data centres
β Industrial process plants
π οΈ How NKD-Type Integrators Typically Implement This
In real projects this usually involves:
- Selecting correct Micrologic variant
- Designing CT placement
- Setting earth fault pickup + delay
- Functional trip testing
- Injection testing
- Coordination with upstream HV protection
π When to Use Dedicated REF Relay Instead
Still recommended when:
- HV transformer differential schemes
- Generator primary protection
- High stability protection required
- Multiple CT schemes required
