MTZ2 08H1, 800 A, 3P drawout, Micrologic 2.0
- Description
- Size Guide
- More Products
Description
Range | MasterPacT |
---|---|
product name | MasterPact MTZ2 |
Device short name | MTZ2 08 H1 |
Product or component type | Circuit breaker |
Device application | Power distribution protection |
Poles description | 3P |
Control unit | Micrologic 2.0 |
Product compatibility | control unit MicroLogic 2.0 X control unit MicroLogic 5.0 X control unit MicroLogic 6.0 X control unit MicroLogic 7.0 X control unit MicroLogic 2.0 Xi control unit MicroLogic 5.0 Xi control unit MicroLogic 6.0 Xi control unit MicroLogic 7.0 Xi |
[In] rated current | 800 A at 40 °C |
Performance type | H1 66 kA 415 V AC |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Selectivity category | Category B |
Control type | Push-button |
Mounting mode | Drawout |
[Icu] rated ultimate short-circuit breaking capacity | 66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz |
---|---|
[Ics] rated service breaking capacity | 66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz |
[Icw] rated short-time withstand current | 66 kA 0.5 s 66 kA 1 s 36 kA 3 s |
[Icm] rated short-circuit making capacity | 145 kA 220/415 V AC at 50/60 Hz 145 kA 440 V AC at 50/60 Hz 145 kA 500/525 V AC at 50/60 Hz 145 kA 660/690 V AC at 50/60 Hz |
Sensor rating | 400 A 630 A 800 A |
[Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 12 kV |
Power dissipation in W | 100 W |
Maximum breaking time | 25 ms |
Maximum closing response time | 70 ms |
Mounting support | Rails Base plate |
Upside connection | Front Rear |
Downside connection | Front Rear |
Connection pitch | 115 mm |
Mechanical durability | 25000 cycles with periodic preventive maintenance |
Electrical durability | 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 |
Height | Drawout circuit breaker with chassis: 439 mm Drawout circuit breaker without chassis: 300 mm |
Width | Drawout circuit breaker with chassis: 441 mm Drawout circuit breaker without chassis: 378 mm |
Depth | Drawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 300 mm |
Product weight | 90 kg |